Refrigerants Quiz

GIFSQ ID: ART-1582

Test your knowledge with this free 20-question Refrigerants quiz from Refrigeration, Freezing & Cold Chain, part of…

What this quiz covers

A refrigerant is the heat transfer medium of the vapour compression cycle: it absorbs heat by evaporating at low pressure and rejects it by condensing at high pressure. This quiz is a tour of the refrigerants themselves, starting with the two environmental metrics that now drive selection. ODP is ozone depletion potential, GWP is global warming potential relative to carbon dioxide, and the two together explain the regulatory map: HFCs such as R404A and R134a have zero ODP but high GWP and are being phased down under the 2016 Kigali Amendment, while HCFC-22, R22, is phased out under the Montreal Protocol.

The questions name the refrigerants by their ASHRAE designations: ammonia is R717, carbon dioxide is R744, and both are natural refrigerants with near zero GWP. HFOs are the newer synthetic class with near zero GWP, developed as replacements for HFCs. Safety classifications follow ASHRAE Standard 34: the letter rates toxicity, A lower and B higher, and the number rates flammability, 1 non flammable to 3 highly flammable, with L for lower burning velocity. That is why ammonia systems need steel construction, since ammonia corrodes copper, plus ventilation and leak detection, and why hydrocarbon refrigerants like propane, class A3, are limited by flammability and charge size limits.

The system is only as good as its charge

The operating questions cover the faults that cost plants money: undercharge shows as low suction pressure with high superheat and reduced capacity, air and other non condensables raise condensing pressure and energy use until purged, moisture forms acids and ice that block expansion devices, and compressor oil must be returned by oil separators and correct piping. Zeotropic blends fractionate on leakage, shifting composition and performance, and temperature glide is the range over which such a blend evaporates or condenses at constant pressure. Servicing rules close the loop: refrigerant is recovered with certified equipment for reclamation or destruction, never vented.

How to use this quiz

Take the quiz cold first, then read the explanations below the player. Each answer gives the reason behind the key, with the refrigerant rules a refrigeration engineer must know.

Refrigerants Quiz
Uncategorized

Choose how you want to play

Sound effects
🔈 Volume
Show explanations
🔊 Auto-read every question
Reading speed

A short note: refrigerants in food plants

A refrigerant is the working fluid of a refrigeration system, taking in heat by evaporating at low pressure and giving it out by condensing at high pressure. Two ratings drive the choice: ozone depletion potential, ODP, and global warming potential, GWP, warming measured against carbon dioxide.

The families tell the story. CFCs such as R12 carry high ODP and left under the Montreal Protocol. HCFC-22, R22, still harms ozone and is phased out too. HFCs such as R404A and R134a spare ozone yet warm strongly, so the Kigali Amendment phases them down. HFOs, hydrofluoro-olefins, offer near-zero GWP and are the newer class. Natural fluids are back in use: ammonia is R717 and carbon dioxide is R744.

ASHRAE Standard 34, mirrored by ISO 817, sets the safety grouping. The letter gives toxicity, A for lower and B for higher, and the number gives flammability, 1 for no flame spread, 2L for lower burning speed, 2 for flammable and 3 for higher flammability. Propane and other hydrocarbons burn readily, class A3, which limits charge sizes.

Ammonia needs steel pipework, ventilation and leak detection, though its sharp smell warns of leaks early. Keep moisture and air out: moisture makes acids and ice that choke expansion devices, and air lifts condensing pressure and energy use. At service or decommissioning, recover refrigerant with certified gear for reclamation or destruction, never vent it.

Check ODP, GWP and the ASHRAE safety group before specifying any refrigerant.

Questions and answers

Note: the player shuffles the questions and the answer options on every attempt, so the numbers in the player will not match the numbers in the questions and answers below. Match each answer by its wording.

Question 1: What are the symptoms of refrigerant undercharge?

  • A. High suction pressure
  • B. Low suction pressure with high superheat and reduced capacity
  • C. No symptoms
  • D. Louder compressor only

Correct answer: Low suction pressure with high superheat and reduced capacity

With too little refrigerant, the evaporator starves, so suction pressure falls while the limited refrigerant picks up excess heat, driving superheat up and cutting capacity. Low suction pressure plus high superheat is the classic undercharge signature.

Question 2: How is compressor lubricating oil managed in a refrigeration system?

  • A. Oil is not used
  • B. It never leaves
  • C. Oil separators and correct piping return oil to the compressor
  • D. Oil stays in the evaporator

Correct answer: Oil separators and correct piping return oil to the compressor

Compressor oil is carried around the circuit with the refrigerant, so systems use oil separators and correctly pitched piping to return oil to the compressor crankcase. Without oil-return management, the compressor would run dry and seize.

Question 3: How is an ammonia leak typically detected first in a plant?

  • A. It makes noise
  • B. Its pungent smell gives early warning of leaks
  • C. It is odorless
  • D. It is visible

Correct answer: Its pungent smell gives early warning of leaks

Ammonia has a sharp, pungent odor detectable at very low concentrations, well below hazardous levels. That smell is the plant's built-in early warning : leaks are noticed by nose before instruments or visible signs.

Question 4: What does ODP stand for in refrigerant selection?

  • A. Operating design pressure
  • B. Oil distribution point
  • C. Overpressure device
  • D. Ozone depletion potential

Correct answer: Ozone depletion potential

ODP stands for ozone depletion potential: a refrigerant's capacity to destroy stratospheric ozone, expressed relative to CFC-11. It is one of the two environmental metrics (alongside GWP) that drive refrigerant selection.

Question 5: Which refrigerant is designated R717?

  • A. R134a
  • B. Ammonia (R717)
  • C. R22
  • D. R404A

Correct answer: Ammonia (R717)

Under the ASHRAE Standard 34 numbering system, ammonia is designated R717 (700 plus its molecular mass of 17). It is the long-standing industrial refrigerant for large food-plant systems.

Question 6: Why must air (non-condensables) be purged from a refrigeration system?

  • A. They raise condensing pressure and energy use
  • B. They cool better
  • C. They have no effect
  • D. They improve efficiency

Correct answer: They raise condensing pressure and energy use

Air and other non-condensables collect in the condenser, where they blanket heat-transfer surfaces and force the compressor to work against higher condensing pressure. Purging them restores normal pressure and cuts energy use.

Question 7: What does the refrigerant do in a refrigeration system?

  • A. To insulate pipes
  • B. To lubricate the compressor
  • C. To absorb heat by evaporating at low pressure and reject it by condensing at high pressure
  • D. To clean the coils

Correct answer: To absorb heat by evaporating at low pressure and reject it by condensing at high pressure

The refrigerant is the heat-transfer medium of the vapor-compression cycle: it boils at low pressure in the evaporator to absorb heat, then is compressed and condensed at high pressure to reject that heat outside. It neither insulates nor lubricates.

Question 8: What is a drawback of zeotropic refrigerant blends?

  • A. They fractionate on leakage, shifting composition and performance
  • B. They cannot be used
  • C. They never leak
  • D. They are always efficient

Correct answer: They fractionate on leakage, shifting composition and performance

Zeotropic blends are mixtures of components with different boiling points, so a leak lets the more volatile components escape first. The remaining charge shifts composition, which changes capacity, pressures, and glide behavior.

Question 9: How must refrigerant be handled when a system is serviced or decommissioned?

  • A. Vented to air
  • B. Burned
  • C. Recovered with certified equipment for reclamation or destruction
  • D. Poured down drains

Correct answer: Recovered with certified equipment for reclamation or destruction

Refrigerants are potent greenhouse gases and ozone depleters, so regulations (e.g., US EPA Clean Air Act §608) require them to be recovered with certified equipment during service and decommissioning, then reclaimed or destroyed. Venting to air is prohibited.

Question 10: What is 'temperature glide' in a refrigerant blend?

  • A. Compressor vibration
  • B. Oil foaming
  • C. Pipe corrosion
  • D. The temperature range over which a blend evaporates/condenses at constant pressure

Correct answer: The temperature range over which a blend evaporates/condenses at constant pressure

Temperature glide is the range of temperatures over which a zeotropic blend evaporates or condenses at constant pressure, caused by its components boiling at different points. Pure fluids and azeotropes have essentially zero glide.

Question 11: What material and safety provisions does an ammonia system require?

  • A. Only paint
  • B. Steel construction (ammonia corrodes copper), ventilation and leak detection
  • C. Larger compressors
  • D. No special measures

Correct answer: Steel construction (ammonia corrodes copper), ventilation and leak detection

Ammonia attacks copper and copper alloys, so ammonia systems are built in steel, and because ammonia is toxic, plants add mechanical ventilation and fixed leak detection. Standard compressors alone address neither hazard.

Question 12: Why must moisture be kept out of a refrigeration circuit?

  • A. It forms acids and ice that block expansion devices
  • B. It has no effect
  • C. It lubricates
  • D. It improves cooling

Correct answer: It forms acids and ice that block expansion devices

Moisture in the circuit reacts with refrigerant and oil to form corrosive acids, and it can freeze at the expansion valve, blocking flow. Keeping the system dry protects both the metal and the metering device.

Question 13: Which newer refrigerant class offers near-zero GWP?

  • A. Ammonia
  • B. HFOs (hydrofluoro-olefins)
  • C. CFCs
  • D. HCFCs

Correct answer: HFOs (hydrofluoro-olefins)

HFOs (hydrofluoro-olefins) are the newer synthetic refrigerant class developed as near-zero-GWP replacements : for example R1234yf and R1234ze(E) have GWPs near 1. The word 'newer' is what distinguishes them from older near-zero-GWP refrigerants such as ammonia and CO₂.

Question 14: Which refrigerant family has zero ODP but high GWP and is being phased down?

  • A. Propane
  • B. Carbon dioxide
  • C. Ammonia
  • D. HFCs such as R404A and R134a

Correct answer: HFCs such as R404A and R134a

HFCs such as R404A and R134a have zero ODP but high GWPs (thousands of times CO₂ over 100 years, per IPCC AR5), so the 2016 Kigali Amendment to the Montreal Protocol mandates their phasedown. Propane, CO₂, and ammonia are not the phased-down family.

Question 15: What is the regulatory status of HCFC-22 (R22)?

  • A. It is encouraged
  • B. It is the best choice
  • C. It has no regulation
  • D. It is phased out under the Montreal Protocol

Correct answer: It is phased out under the Montreal Protocol

HCFC-22 (R22) depletes ozone, so the Montreal Protocol's accelerated HCFC schedule ended its production and consumption in developed countries by 2020. It is phased out, not encouraged.

Question 16: What do ASHRAE safety classifications like A1 and B2L indicate?

  • A. Color codes
  • B. Pressure ratings
  • C. Pipe sizes
  • D. Toxicity (A/B) and flammability (1/2/3, with L for lower burning velocity)

Correct answer: Toxicity (A/B) and flammability (1/2/3, with L for lower burning velocity)

Under ASHRAE Standard 34, the letter rates toxicity (A = lower toxicity, B = higher toxicity) and the number rates flammability (1 = non-flammable, 2 = flammable, 3 = highly flammable), with 'L' marking lower burning velocity. A1 is thus low-toxicity non-flammable; B2L is higher-toxicity, mildly flammable.

Question 17: What is GWP and why does it drive refrigerant choices?

  • A. Global warming potential relative to carbon dioxide
  • B. Gas withdrawal point
  • C. General working pressure
  • D. Gross weight of product

Correct answer: Global warming potential relative to carbon dioxide

GWP : global warming potential : expresses how much heat a greenhouse gas traps relative to carbon dioxide over a set horizon (usually 100 years). It is the metric behind HFC phasedowns and low-GWP refrigerant rules.

Question 18: Why do food plants use secondary refrigerant (glycol) loops?

  • A. They are decorative
  • B. They increase charge
  • C. They circulate a secondary fluid so the primary refrigerant charge stays in the plant room
  • D. They eliminate insulation

Correct answer: They circulate a secondary fluid so the primary refrigerant charge stays in the plant room

A secondary glycol loop circulates chilled glycol to the process areas, so the primary refrigerant charge stays confined to the plant room. That keeps large refrigerant inventories out of food areas and simplifies leak management.

Question 19: What limits the use of hydrocarbon refrigerants like propane?

  • A. They are flammable (A3), limiting charge sizes
  • B. They are toxic
  • C. They destroy ozone
  • D. They are inefficient

Correct answer: They are flammable (A3), limiting charge sizes

Hydrocarbons like propane are classified A3 under ASHRAE Standard 34 : low toxicity but highly flammable : so standards such as EN 378/ISO 5149 strictly limit allowable charge sizes. Flammability, not toxicity or ozone impact, is the constraint.

Question 20: Which refrigerant is designated R744?

  • A. Ammonia
  • B. Water
  • C. Carbon dioxide (R744)
  • D. Propane

Correct answer: Carbon dioxide (R744)

Under ASHRAE Standard 34's inorganic-refrigerant numbering (700 plus molecular mass), carbon dioxide (molecular mass 44) is designated R744. It is the natural refrigerant widely used in transcritical supermarket and food-plant systems.